Streamlined Structure & Expansion Flexibility
- The 10kV Compact Box Type Substation launched by Kechang Electric adopts the State Grid standard streamlined design, removes redundant switch components, and controls the size of the box at 2.65m in length ×1.35m in width×2.1m in height.
- At the same time, a standardized expansion interface is reserved. The low-voltage outlet can be expanded from 4 channels to 6 channels, and the compensation capacity can be flexibly adjusted according to the rated capacity of the transformer. 10%-15%, without the need to replace the box as a whole, it perfectly solves the contradiction between "limited space" and "late expansion", and adapts to scenarios where the load is gradually increasing.
Product Advantages

1. Compact structure, support flexible expansion in the later stage
The overall structure is highly streamlined, which greatly reduces the footprint compared to traditional box changes. The equipment reserves a standardized expansion interface, and the low-voltage outlet circuit can be expanded from 4 channels to 6 channels; the reactive power compensation capacity can be flexibly adjusted in the range of 10%-15% according to the rated capacity of the transformer, without the need to replace the box as a whole. It is perfectly adapted to the working conditions where the load is gradually increasing, avoiding repeated procurement of equipment in the project, and saving input costs.
2. Intelligent anti-condensation, stable operation around the clock
In view of the problem that underground garages and low-lying humid sites are prone to condensation and insulation failure, the equipment is equipped with an intelligent dehumidification system. The temperature and humidity sensor links the heater with the directional ventilation tank to automatically control the humidity in the box within 60%. The box adopts an upper air outlet and lower air inlet ventilation structure and is equipped with a dust-proof filter, which not only guarantees the natural heat dissipation effect, but also prevents dust from entering. The protection level is IP54, and it can work stably in an environment of -25℃~45℃ and 95% relative humidity, without the need for regular manual dehumidification and maintenance.


3. Ultra-fast arc protection, improve operating safety level
Built-in high-sensitivity arc light sensor, response time ≤2ms, can instantly capture arc faults in the box, quickly trigger tripping, and shorten the arc combustion time. The pressure relief channel of the box body is preset to release the internal impact pressure in time to eliminate the risk of bursting of the box body. The internal insulation parts are made of F1-grade flame-retardant epoxy resin, which has passed the IEC 60298 anti-arc test, which effectively avoids equipment damage and personal safety accidents, and is suitable for power distribution projects in densely populated areas.
4. Accurate reactive power compensation, stable output voltage
Equipped with a modular reactive power compensation unit, it can accurately match the compensation capacity, support phase separation compensation, effectively suppress three-phase imbalance and voltage fluctuations, and maintain a stable power factor above 0.95. The impedance of the transformer has been optimized, the impedance and voltage deviation are controlled within ±5%, and the voltage regulation rate is ≤±2% when the load is switched, which provides a stable power supply for industrial and commercial precision equipment.The products comply with the 2020 version of the State grid design specifications and IEC 60076 standards, have CE and RoHS certifications, and come with a full set of factory withstand voltage and local discharge test reports, which are convenient for project acceptance and docking.

Arc Flash Protection & Safety Enhancement
Arc failure inside the box transformer can easily cause equipment damage and casualties, and buyers have an urgent need for precise protection.The product has a built-in arc flash detection sensor with a response time of ≤2ms. It can quickly capture the arc optical signal and activate the fast tripping module to limit the arc combustion time. At the same time, the box body reserves a pressure relief channel to quickly release the internal pressure and avoid the box body exploding.The internal insulating parts are cast with F1-grade flame-retardant epoxy resin and have passed the IEC 60298 anti-arc light test, which greatly improves operating safety and adapts to the surrounding power distribution scene in densely populated areas.

Precision Compensation & Voltage Stability
Buyers attach importance to the voltage stability of the power distribution system to avoid terminal equipment failure due to load fluctuations.
The product is equipped with a modular reactive power compensation module, the compensation capacity can be accurately matched according to the rated capacity of the transformer, and supports phase separation compensation, which can effectively suppress three-phase imbalance and voltage fluctuations, and stabilize the power factor above 0.95.
At the same time, the impedance design of the transformer is optimized, and the impedance voltage deviation is controlled within ±5% to ensure that the voltage regulation rate is ≤±2% when the load is switched, which is suitable for commercial and industrial scenarios where precision equipment is concentrated.
Standard Compliance & Custom Support
Project acceptance and personalized adaptation are the core concerns of buyers.
Kechang Electric strictly follows the 2020 version of the State Grid standardized design plan and IEC 60076 standard production, and has passed CE and RoHS certification. Each equipment comes with a complete factory withstand voltage and local discharge test report, which can be directly adapted to the State Grid supporting project acceptance.
Product Specifications
| Project | Unit | Parameter | ||
| High pressure side |
Rated frequency | Hz | 50 | |
| Rated voltage | KV | 6/10/35 | ||
| Maximum operating voltage | KV | 6.9/11.5/40.5 | ||
| Rated current | A | 400/630/1250 | ||
| Transfer current | A | 1200-3150 | ||
| Rated short-circuit switch current (current-limiting fuse) | KA | 25-50 | ||
| Transformer | Rated voltage | KV | 50 | |
| Rated capacity | KVA | 30-2000 | ||
| Tap range | % | ±2*2.5/±5% | ||
| Connection group | Yyn0/Dyn11 | |||
| Impedance voltage | % | 4.4/5.6/8 | ||
| Low pressure side |
Rated voltage | V | 220/380/690/800 | |
| Main circuit rated current | A | 50-4000 | ||
| Branch current | A | 5-800 | ||
| case | Protection level | IP23/IP33/IP65 | ||
| Noise level(dB) | ≤50 | |||
Hot Tags: compact box type substation, China compact box type substation manufacturers, suppliers, factory, 500 kva compact substation, Compact Transformer Substation, compact substation transformer, Compact Box Type Substation, kiosk type substation, compact unit substation