Products Description

Integrated Design Lowers Compatibility Risks
As a key 12kV medium-voltage product of Kechang Electrical, the Embedded Poles Type Vacuum Circuit Breaker is specifically designed for compact switchgear, ring main units, and power grid renovation projects. Built on Kechang's mature vacuum switching technology and production experience, it integrates vacuum interrupter, conductive components, and insulation support into an integrated embedded pole. For buyers, it solves the critical pain point of incompatible parts and assembly errors with traditional split-type breakers, ensuring seamless matching with your existing switchgear and reducing on-site installation risks.
Ensures Long-Term Insulation Stability
Adopting precision epoxy resin integral casting, the embedded pole forms a seamless, airtight insulation structure. This design completely isolates internal components from moisture, dust, and corrosive gases, avoiding insulation degradation and partial discharge risks. Each pole undergoes strict dielectric strength and temperature cycle tests before delivery, complying with national standards. This solves your worry about frequent insulation maintenance and unexpected power outages, extending the product's service life to over 15 years.


Reduces Lifecycle O&M Costs
Benefiting from the sealed embedded pole design, the breaker's core components (vacuum interrupter, contacts) are free from external environmental erosion, requiring no regular cleaning or vacuum degree detection. The matched modular operating mechanism, with a mechanical life of 3000 operations, also minimizes wear and tear. This solves your problem of high maintenance labor and part replacement costs, significantly reducing the total operational cost throughout the product's life.
Optimizes Switchgear Space Utilization
Equipped with high-integration pole layout, the breaker's volume is reduced by 30% compared to traditional split-type products. Its compact structure allows for smaller switchgear design, which is particularly suitable for urban substations, high-rise building electrical rooms, and other space-constrained scenarios. For buyers, this not only cuts switchgear manufacturing and installation costs but also simplifies transportation and storage, lowering logistics expenses.


Meets Diverse Project Needs
Leveraging Kechang's professional 12kV product customization capability, the breaker supports flexible configuration of rated current (630A-4000A) and auxiliary voltage (AC/DC 110V/220V) according to your project requirements. It can also be tailored with additional functions such as auxiliary contacts and interlock devices to match specific protection needs. Our pre-sales technical team will conduct in-depth communication to confirm your grid parameters and switchgear models, ensuring the product perfectly fits your project and avoiding over-purchase or insufficient performance.
Rigorous Quality Control & Comprehensive After-Sales
Each breaker passes multi-stage strict inspections (including vacuum degree test, mechanical performance test, and insulation test) in Kechang's professional laboratory, complying with national standards and industry acceptance criteria. We provide a 3-year quality warranty for core components, along with pre-sales technical consultation, on-site installation guidance, and long-term spare parts supply. Backed by Kechang's reliable after-sales network, this solves your concerns about product quality and post-purchase maintenance, ensuring worry-free procurement and operation.

Product Features
Integrated Embedded Structure for Superior Insulation Performance
Molded with epoxy resin, the arc extinguishing chamber, conductive circuit, and insulation components are integrated and encapsulated. The insulation tube features an inner skirt and reinforcement ribs, improving insulation performance and dynamic current resistance. The long-term insulation stability far exceeds that of traditional split-type circuit breakers.
Compact Size, High Space Utilization
Compared to traditional split-pole circuit breakers, the embedded structure significantly simplifies external connections and supporting components, reducing the overall device size by over 30%. This more compact size allows for flexible adaptation to various indoor switchgear (such as the KYN28).

Products Drawing

Operating Environment
- Ambient Temperature
- Maximum: +40°C
- Minimum: -15°C
- Daily average: no more than +35°C
- Altitude: no more than 1000m
- Humidity:
- Daily average relative humidity ≤ 95%
- Monthly average relative humidity ≤ 90%
- Seismic intensity: no more than 8 degrees
- Embedded poles type vacuum circuit breaker available in a location free from dripping water, steam, flammable gases, fire, explosion hazards, chemical corrosion, and severe vibration.

Product Specifications
| Number | Parameter name | Unit | Technical Parameters | |||
| 1 | Rated voltage | kV | 12 | |||
| 2 | Rated short-time frequency withstand voltage (1 min) | kV | 42 | |||
| 3 | Rated lightning impulse withstand voltage (peak) | kV | 75 | |||
| 4 | Rated frequency | Hz | 50 | |||
| 5 | Rated current | A | 630/1250/1600/2000/2500/3150/4000 | |||
| 6 | Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | 40 |
| 7 | Rated short-time withstand current | kA | 20 | 25 | 31.5 | 40 |
| 8 | Rated short circuit duration | S | 4 | |||
| 9 | Rated short-circuit closing current | kA | 50 | 63 | 80 | 100 |
| 10 | Rated peak withstand current | kA | 50 | 63 | 80 | 100 |
| 11 | Number of rated short-circuit current starts | times | 30 | 30 | 30 | 20 |
| 12 | Rated individual capacitor bank opening current | A | ≤630 | |||
| 13 | Rated back-to-back capacitor bank opening current | A | ≤400 | |||
| 14 | Rated capacitor bank closing inrush current | kA | 12.5(frequency≤1000Hz) | |||
| 15 | Closing time | ms | ≤80 | |||
| 16 | Split time | ms | Maximum Voltage | ≤40 | ||
| ms | Rated Voltage | ≤50 | ||||
| ms | Minimum Voltage | ≤60 | ||||
| 17 | Time of ignition | ms | ≤15 | |||
| 18 | Mechanical life (M2) | times | 30000 | |||
| 19 | Allowable cumulative thickness of dynamic and static contact wear | mm | 3 | |||
| 20 | Rated closing operating voltage | V | AC/DC 220, AC/DC 110 | |||
| 21 | Rated breaking operating voltage | V | AC/DC 220, AC/DC 110 | |||
| 22 | Rated operating voltage of energy storage motor | V | AC/DC 220, AC/DC 110 | |||
| 23 | Rated power of energy storage motor | W | 80 (40KA Motor speed 100W) | |||
| 24 | Energy storage time | s | ≤15 | |||
| 25 | Contact opening distance | mm | 9±1 | |||
| 26 | Over traveling distance | mm | 3.5±0.5 | |||
| 27 | Contact closing bounce time | ms | ≤2 | |||
| 28 | Three-phase switching and closing non-synchronous | ms | ≤2 | |||
| 29 | Contact splitting rebound amplitude | mm | ≤3 | |||
| 30 | Contact closing contact pressure | kA | 20 | 25 | 31.5 | 40 |
| N±8% | 2200 | 2500 | 3100 | 4750 | ||
| 31 | Average breaking speed (contacts separated by 6mm) | m/s | 1.1±0.2 | |||
| 32 | Average closing speed (6mm contact closure) | m/s | 0.6±0.2 | |||
| 33 | Dominant electric circuit resistance | A | 630 | 1250 | 1600-2000 | ≥2500 |
| 34 | μΩ | ≤50 | ≤45 | ≤35 | ≤25 | |
| Rated operating sequence (1) 20~31.5KA | Minutes - 0.3s - combined minutes - 180s - combined minutes | |||||
| 35 | Rated sequence of operation (2) 40KA | Minutes - 0.3s - combined minutes - 180s - combined minutes | ||||
| Secondary circuit frequency withstand voltage (1min) | V | 2000 | ||||
Hot Tags: embedded poles type vacuum circuit breaker, China embedded poles type vacuum circuit breaker manufacturers, suppliers, factory, outdoor circuit breaker, hv circuit breaker, dc circuit breaker, blown circuit breaker, standard circuit breaker, industrial circuit breaker