Products Introduction
Indoor Solid Sealed Vacuum Circuit Breaker uses advanced APG automatic pressure gel technology to integrally cast the vacuum interrupter and main circuit into a fully enclosed solid‑sealed pole with high‑performance epoxy resin. It features ultra‑high insulation strength, self‑convection heat dissipation, full EMC compliance, online mechanical status monitoring, maintenance‑free design, and long service life. It is widely used in industrial plants, urban power grids, data centers, petrochemical, mining, and unattended substations.

Products Advantages

APG Solid Insulation Craftsmanship
- One‑piece casting by APG automatic pressure gel process
- Epoxy resin insulation strength: 5–6 times that of air
- Partial discharge strictly controlled below 10pC
- Built‑in buffer layer resists electric stress & environmental erosion
- Completely solves pollution, condensation & insulation failure
Integrated Mechanical Status Monitoring
- Built‑in stroke sensor & coil current sensor
- Online monitoring of opening/closing & coil waveform
- Real‑time capture of mechanical stagnation & coil abnormality
- Transforms maintenance: "breakdown repair" → "predictive maintenance"


Maintenance-Free & Long Service Life
- Fully sealed structure; no regular cleaning, oiling or insulation replacement
- Mechanical life ≥30,000 times; electrical life ≥20,000 times
- Service life up to 25 years
- 12‑months warranty; free replacement of core components under quality defect
- Ideal for unattended substations
Flexible Voltage Grade Customization
- Customizable: 12kV / 24kV / 40.5kV
- Adjustable dimensions & mounting interfaces
- Adapt to vertical / handcart / side‑mounted installation
- Optimized for high altitude & extreme cold
- ustom solution & quotation within 48 hours

why choose us

why choose our products
✅ 18 years of R&D & export experience; mature production & quality system
✅Full process inspection; products meet/exceed national & international standards
✅Professional R&D team; fast customized solutions for parameters & structure
✅Full life cycle support: pre‑sales consultation, on‑site commissioning, after‑sales warranty
✅ 48h quick response for voltage, current, installation, structu
FAQ
Q: What are the customizable currents of indoor solid sealed vacuum circuit breaker ?
A:630A/1250A/1600A/2000A/2500A/3150A/4000A
Q: What kind of installation method is there?
A:Withdrawable type/Fixed type/Side mounted type
Q: What shipping methods are available?
A: We offer various shipping methods, including air, sea, truck, and rail.
Q: Do you test your products?
A: Our products undergo rigorous factory testing and are shipped only after passing inspection.
Technical Specification
| Number | Parameter name | Unit | Technical Parameters | |||
| 1 | Rated voltage | kV | 12 | |||
| 2 | Rated short-time frequency withstand voltage (1 min) | kV | 42 | |||
| 3 | Rated lightning impulse withstand voltage (peak) | kV | 75 | |||
| 4 | Rated frequency | Hz | 50 | |||
| 5 | Rated current | A | 630/1250/1600/2000/2500/3150/4000 | |||
| 6 | Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | 40 |
| 7 | Rated short-time withstand current | kA | 20 | 25 | 31.5 | 40 |
| 8 | Rated short circuit duration | S | 4 | |||
| 9 | Rated short-circuit closing current | kA | 50 | 63 | 80 | 100 |
| 10 | Rated peak withstand current | kA | 50 | 63 | 80 | 100 |
| 11 | Number of rated short-circuit current starts | times | 30 | 30 | 30 | 20 |
| 12 | Rated individual capacitor bank opening current | A | ≤630 | |||
| 13 | Rated back-to-back capacitor bank opening current | A | ≤400 | |||
| 14 | Rated capacitor bank closing inrush current | kA | 12.5(frequency≤1000Hz) | |||
| 15 | Closing time | ms | ≤80 | |||
| 16 | Split time | ms | Maximum Voltage | ≤40 | ||
| ms | Rated Voltage | ≤50 | ||||
| ms | Minimum Voltage | ≤60 | ||||
| 17 | Time of ignition | ms | ≤15 | |||
| 18 | Mechanical life (M2) | times | 30000 | |||
| 19 | Allowable cumulative thickness of dynamic and static contact wear | mm | 3 | |||
| 20 | Rated closing operating voltage | V | AC/DC 220, AC/DC 110 | |||
| 21 | Rated breaking operating voltage | V | AC/DC 220, AC/DC 110 | |||
| 22 | Rated operating voltage of energy storage motor | V | AC/DC 220, AC/DC 110 | |||
| 23 | Rated power of energy storage motor | W | 80 (40KA Motor speed 100W) | |||
| 24 | Energy storage time | s | ≤15 | |||
| 25 | Contact opening distance | mm | 9±1 | |||
| 26 | Over traveling distance | mm | 3.5±0.5 | |||
| 27 | Contact closing bounce time | ms | ≤2 | |||
| 28 | Three-phase switching and closing non-synchronous | ms | ≤2 | |||
| 29 | Contact splitting rebound amplitude | mm | ≤3 | |||
| 30 | Contact closing contact pressure | kA | 20 | 25 | 31.5 | 40 |
| N±8% | 2200 | 2500 | 3100 | 4750 | ||
| 31 | Average breaking speed (contacts separated by 6mm) | m/s | 1.1±0.2 | |||
| 32 | Average closing speed (6mm contact closure) | m/s | 0.6±0.2 | |||
| 33 | Dominant electric circuit resistance | A | 630 | 1250 | 1600-2000 | ≥2500 |
| 34 | μΩ | ≤50 | ≤45 | ≤35 | ≤25 | |
| Rated operating sequence (1) 20~31.5KA | Minutes - 0.3s - combined minutes - 180s - combined minutes | |||||
| 35 | Rated sequence of operation (2) 40KA | Minutes - 0.3s - combined minutes - 180s - combined minutes | ||||
| Secondary circuit frequency withstand voltage (1min) | V | 2000 | ||||
Hot Tags: indoor solid sealed vacuum circuit breaker, China indoor solid sealed vacuum circuit breaker manufacturers, suppliers, factory, outdoor circuit breaker, hv circuit breaker, dc circuit breaker, blown circuit breaker, standard circuit breaker, industrial circuit breaker