Electrical Vacuum Breaker

Electrical Vacuum Breaker

Details
Rated Voltage:10KV 35KV 66KV
Rated Current:630A 1250A 2000A
Rated Breaking Capacity:25kA 31.5kA 40kA
Operation Mechanism:Spring-Operated/Electromagnetic
Protection Level:IP44 IP54
Frequency:50Hz 60Hz
Insulation Level:LI75kV/AC35kV LI170kV/AC70kV
Category
Circuit Breaker
Share to
Send Inquiry
Description
Technical Parameters

1. Product Introduction

Kechang's core advantage is vacuum arc extinguishing technology. Its arc extinguishing chamber uses a high vacuum environment to extinguish the arc in less than 20 milliseconds when the current crosses zero, quickly cutting off short-circuit faults. The spiral contacts with transverse magnetic field design reduce ablation and extend service life, providing reliable grid protection.

product-501-483

2. Product Advantages

product-404-400

Maintenance-Free Design Cuts OPEX

Equipped with a fully sealed vacuum arc extinguishing chamber, the internal components of the equipment are completely isolated from the external environment. This means you won't need to perform regular cleaning or replace parts. The core spring operating mechanism has undergone strict testing, boasting a mechanical life of up to 30,000 times-no lubrication or maintenance is required at all. Compared with traditional equipment that needs inspection and maintenance at least twice a year, this one can cut on-site maintenance workload by 90%, effectively reducing OPEX. It's especially well-suited for projects where frequent maintenance is difficult to carry out.

Wide Temperature Range & High Protection

The equipment features an IP44 protection level, with a thickened anti-corrosion galvanized steel shell and a tight sealing structure. These designs effectively keep out dust, water vapor and corrosive gases. It can operate stably in a temperature range of -25℃ to 45℃, even at an altitude of 2000 meters and a relative humidity of 95%, without the need for additional protective devices. Its internal insulation components are made of Class H (180℃) materials, which can withstand high temperatures for a long time and are not easy to age-perfect for stable operation in both peak summer heat and cold winter conditions.

product-6000-4000
 

High quality Indoor high voltage vacuum circuit breaker

Low Noise & Flame Retardant Safety

For places like commercial buildings, hospitals and data centers, equipment noise and fire safety are crucial. We've optimized the equipment's operating mechanism and added shock absorption components, so the operating noise is controlled below 45dB, which meets IEC noise standards. Even if installed in a power distribution room near offices or residential areas, it won't cause any interference. The entire machine adopts an oil-free design, and its core insulation components are cast with F1-grade flame-retardant epoxy resin-this completely eliminates hidden dangers of oil leakage and fire. It has passed IEC 60076 fire certification, fully meeting the high safety requirements of densely populated areas.

3. Product Application

 

Chinese factpry Indoor high voltage vacuum circuit breaker

 

4. Operating Environment

 

  • Ambient temperature
  • Maximum temperature:+40℃ Minimum temperature:-15℃
  • Daily average value is not more than +35℃ Altitude: not more than 1000m
  • Daily average relative humidity:≤95% Monthly average relative humidity:≤90%
  • Earthquake intensity: no more than 8 degrees
  • And places without dripping water, steam, flammable gas, fire, explosion danger, chemical corrosion and severe vibration.
  • The vacuum arc chamber adopts reliable metallization process and welding structure, which can operate with power for a long time.

 

5. Product Specifications

 

Number Parameter name Unit Technical Parameters
1 Rated voltage kV 12
2 Rated short-time frequency withstand voltage (1 min) kV 42
3 Rated lightning impulse withstand voltage (peak) kV 75
4 Rated frequency Hz 50
5 Rated current A 630/1250/1600/2000/2500/3150/4000
6 Rated short-circuit breaking current kA 20 25 31.5 40
7 Rated short-time withstand current kA 20 25 31.5 40
8 Rated short circuit duration S 4
9 Rated short-circuit closing current kA 50 63 80 100
10 Rated peak withstand current kA 50 63 80 100
11 Number of rated short-circuit current starts times 30 30 30 20
12 Rated individual capacitor bank opening current A ≤630
13 Rated back-to-back capacitor bank opening current A ≤400
14 Rated capacitor bank closing inrush current kA 12.5(frequency≤1000Hz)
15 Closing time ms ≤80
16 Split time ms Maximum Voltage ≤40
ms Rated Voltage ≤50
ms Minimum Voltage ≤60
17 Time of ignition ms ≤15
18 Mechanical life (M2) times 30000
19 Allowable cumulative thickness of dynamic and static contact wear mm 3
20 Rated closing operating voltage V AC/DC 220, AC/DC 110
21 Rated breaking operating voltage V AC/DC 220, AC/DC 110
22 Rated operating voltage of energy storage motor V AC/DC 220, AC/DC 110
23 Rated power of energy storage motor W 80 (40KA Motor speed 100W)
24 Energy storage time s ≤15
25 Contact opening distance mm 9±1
26 Over traveling distance mm 3.5±0.5
27 Contact closing bounce time ms ≤2
28 Three-phase switching and closing non-synchronous ms ≤2
29 Contact splitting rebound amplitude mm ≤3
30 Contact closing contact pressure kA 20 25 31.5 40
N±8% 2200 2500 3100 4750
31 Average breaking speed (contacts separated by 6mm) m/s 1.1±0.2
32 Average closing speed (6mm contact closure) m/s 0.6±0.2
33 Dominant electric circuit resistance A 630 1250 1600-2000 ≥2500
34 μΩ ≤50 ≤45 ≤35 ≤25
Rated operating sequence (1) 20~31.5KA   Minutes - 0.3s - combined minutes - 180s - combined minutes
35 Rated sequence of operation (2) 40KA   Minutes - 0.3s - combined minutes - 180s - combined minutes
Secondary circuit frequency withstand voltage (1min) V 2000

Hot Tags: Electrical Vacuum Breaker, China Electrical Vacuum Breaker manufacturers, suppliers, factory, outdoor circuit breaker, hv circuit breaker, dc circuit breaker, blown circuit breaker, standard circuit breaker, industrial circuit breaker

Send Inquiry
Contact us if have any question

You can either contact us via phone, email or online form below. Our specialist will contact you back shortly.

Contact now!