In many substations, the ring main unit does not get much attention. It stays closed, it switches when told, and most of the time no one looks at it. That is usually a good sign. Kechang Electric designs its Ring Main Unit switchgear for this kind of work. No extra functions. No complicated logic. Just equipment that reacts the way operators expect when something goes wrong.
It is often installed as medium voltage ring main unit switchgear in indoor substations, commercial buildings, and city distribution loops where access is limited and downtime is not acceptable.

Cooling Based on How the Room Actually Feels
Most indoor rooms are not hot all the time. Because of that, the RMU runs with natural air circulation as standard. No fans spinning for no reason. No added parts that may fail later.
If the room gets warm, or the load stays high, forced air cooling can be added. Fans start when the temperature rises and stop again when it drops. Air moves where the heat is. It does not just fill the enclosure. This keeps things under control without turning the RMU into a noisy machine.
Insulation Picked for Long Hours, Not Short Tests
The insulation system is chosen with continuous operation in mind. Some projects run light. Others push the unit hard. Wires heat up, currents stay high. Kechang adds Class F or Class H insulation depending on the load.
Epoxy-coated parts stay solid. They hold voltage, resist sparks, and keep electricity flowing even after long hours. The windings stay tight, insulation stays in place, and the unit keeps running without trips.
Electrical Layout That Avoids Confusion
Operators follow the switches easily. Mechanical interlocks force each step. One breaker opens, the rest keep flowing. The enclosure stays solid. Nothing twists, nothing moves out of place.
Most installations stick to standard distribution levels. Many come as 12kV ring main units. The electrical layout stays simple, and the unit reacts exactly when a fault appears.

Fire Risk Treated as a Basic Requirement
The RMU uses an oil-free design. Epoxy materials stop flames from spreading. That's it.This makes it easy to place in basements, indoor substations, and commercial spaces. Often, you don't need extra fire barriers around the unit.
Noise That Does Not Get Noticed
The unit runs quietly. Fans start only when heat rises. Even then, they spin slow and steady. Offices or shops nearby hear almost nothing.
The RMU works without shouting, even when forced cooling kicks in. Low-noise fans and smooth airflow keep sound in check.
Installation That Adjusts to the Site
Front access lets operators reach cables and panels without crawling behind the unit. They adjust protection, check temperatures, and connect wires fast.
Customization focuses on what affects daily work. Fans, enclosures, voltage ratings, and cable entry can move or swap to fit the space. The RMU stays compact, practical, and ready to run, not bulky or confusing.


Product Specifications
| Project | Parameter | |||
| Load Switchgear (C) | Combined Elecctric Cabinet (F) | Circuit Breaker Cabinet(V) | ||
| Rated Voltage | 12kV | |||
| Rated Frequency | 50HZ | |||
| Rated Current | 630A | 1250A (Depends on Fuse Current) | 630A/1250A | |
| Rated Transfer Current | / | 1750A | / | |
| Cable Charging Break Current | 40A | 25A | ||
| No-load Transformer Breaking Current | 16A | 16A | ||
| Rated Switching Times of Active Load | 100次 | / | / | |
| Rated Number of Short Circuit Breakering | / | / | ≥30 times | |
| Rated Short-time Tolerable Current |
The Primary Loop | 20kA/4S | / | 20kA/4S,31.5kA/4S |
| Grounding Switch | 20kA/4S | / | 20kA/4S,31.5kA/4S | |
| Rated short circuit closing current |
The Primary Loop | 50kA | Limited by High Voltage Fuse | 50kA/80kA |
| Grounding Switch | 50kA | 50kA/80kA | ||
| 1 mimute Power Frequency Voltage Withstand |
Interphase with and against the ground | 42kV | ||
| Fracture | 48kV | |||
| Lighting Shock Withstand Voltage | Interphase with and against the ground | 75kV | ||
| Fracture | 85kV | |||
| Mechanical Life | The Main Switch | ≥5000 times | ≥10000 times | |
| Grounding Switch | ≥3000 times | |||
| Main Circuit Resistance | ≤120μΩ | ≤400μΩ | ≤200μΩ | |
| SF6 Gas Pressure Rating (20℃) | 0.035MPa | |||
| Annual Leakage Rate of SF6 Gas | 0.01% | |||
| Rated Power Supply Voltage of Secondary Loop | AC220V/DC110/DC48V/DC24V | |||
| 1 minute Power Frequency withstand Voltage of Secondary Loop | 2kV | |||
| Protection Grade | Aeration Tank | IP67 | ||
| Shell and Operating Mechanism | IP4X | |||