Products Introduction
Our indoor SF6 circuit breakers are primarily used in indoor high-voltage power distribution systems where safety, reliability, and service life are paramount. They utilize a combination of a vacuum arc extinguishing chamber and SF6 gas insulation, enabling them to reliably and stably perform insulation, arc extinguishing, overload protection, and short-circuit protection functions in various enclosed indoor environments, including high-voltage switchgear, distribution rooms, small substations, commercial buildings, industrial power plants, and urban power grids, providing safe and stable operation assurance for modern indoor high-voltage power distribution systems.

Product Features

1. Indoor SF6 circuit breaker adopts optimized operating mechanism with stable transmission performance, low operating noise and small impact force during opening and closing, effectively reducing mechanical wear and ensuring long-term stable operation under frequent operation conditions.
2. The circuit breaker shell adopts high-strength insulation and anticorrosive materials, has a compact structure and a regular appearance, and is easy to install in standard switchgear such as KYN28 and XGN. The overall seal is good, which can effectively prevent dust and moisture, and ensure stable indoor long-term operation.
3. The frame has high strength and long mechanical life. It can withstand the shock and vibration caused by frequent closing and closing. It is easy to install and fix, and it is suitable for the size of the standard cabinet.
Maintenance and convenient design
Indoor SF6 circuit breaker has extremely low maintenance in daily use, which is more suitable for indoor unattended scenarios.:
The vacuum arc extinguishing chamber is maintenance-free, and the performance of long-term use is not degraded.
SF6 gas seal is reliable, and the air pressure only needs to be checked briefly every day.
Modular structure, faster installation, commissioning, and replacement of parts.
In line with national standards and international standards, compatible with all kinds of switchgear.
Operating environment
Maximum temperature: +40℃
Minimum temperature: -15℃
Daily average value is not more than +35℃
Altitude: not more than 1000m
Daily average relative humidity: ≤95%
Monthly average relative humidity: ≤90%
Earthquake intensity: no more than 8 degrees
And places without dripping water, steam, flammable gas, fire, explosion danger, chemical corrosion and severe vibration.

Product Specifications
| Number | Parameter name | Unit | Technical Parameters | |||
| 1 | Rated voltage | kV | 12 | |||
| 2 | Rated short-time frequency withstand voltage (1 min) | kV | 42 | |||
| 3 | Rated lightning impulse withstand voltage (peak) | kV | 75 | |||
| 4 | Rated frequency | Hz | 50 | |||
| 5 | Rated current | A | 630/1250/1600/2000/2500/3150/4000 | |||
| 6 | Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | 40 |
| 7 | Rated short-time withstand current | kA | 20 | 25 | 31.5 | 40 |
| 8 | Rated short circuit duration | S | 4 | |||
| 9 | Rated short-circuit closing current | kA | 50 | 63 | 80 | 100 |
| 10 | Rated peak withstand current | kA | 50 | 63 | 80 | 100 |
| 11 | Number of rated short-circuit current starts | times | 30 | 30 | 30 | 20 |
| 12 | Rated individual capacitor bank opening current | A | ≤630 | |||
| 13 | Rated back-to-back capacitor bank opening current | A | ≤400 | |||
| 14 | Rated capacitor bank closing inrush current | kA | 12.5(frequency≤1000Hz) | |||
| 15 | Closing time | ms | ≤80 | |||
| 16 | Split time | ms | Maximum Voltage | ≤40 | ||
| ms | Rated Voltage | ≤50 | ||||
| ms | Minimum Voltage | ≤60 | ||||
| 17 | Time of ignition | ms | ≤15 | |||
| 18 | Mechanical life (M2) | times | 30000 | |||
| 19 | Allowable cumulative thickness of dynamic and static contact wear | mm | 3 | |||
| 20 | Rated closing operating voltage | V | AC/DC 220, AC/DC 110 | |||
| 21 | Rated breaking operating voltage | V | AC/DC 220, AC/DC 110 | |||
| 22 | Rated operating voltage of energy storage motor | V | AC/DC 220, AC/DC 110 | |||
| 23 | Rated power of energy storage motor | W | 80 (40KA Motor speed 100W) | |||
| 24 | Energy storage time | s | ≤15 | |||
| 25 | Contact opening distance | mm | 9±1 | |||
| 26 | Over traveling distance | mm | 3.5±0.5 | |||
| 27 | Contact closing bounce time | ms | ≤2 | |||
| 28 | Three-phase switching and closing non-synchronous | ms | ≤2 | |||
| 29 | Contact splitting rebound amplitude | mm | ≤3 | |||
| 30 | Contact closing contact pressure | kA | 20 | 25 | 31.5 | 40 |
| N±8% | 2200 | 2500 | 3100 | 4750 | ||
| 31 | Average breaking speed (contacts separated by 6mm) | m/s | 1.1±0.2 | |||
| 32 | Average closing speed (6mm contact closure) | m/s | 0.6±0.2 | |||
| 33 | Dominant electric circuit resistance | A | 630 | 1250 | 1600-2000 | ≥2500 |
| 34 | μΩ | ≤50 | ≤45 | ≤35 | ≤25 | |
| Rated operating sequence (1) 20~31.5KA | Minutes - 0.3s - combined minutes - 180s - combined minutes | |||||
| 35 | Rated sequence of operation (2) 40KA | Minutes - 0.3s - combined minutes - 180s - combined minutes | ||||
| Secondary circuit frequency withstand voltage (1min) | V | 2000 | ||||