Utility Transformers

Utility Transformers

Details
High Voltage: 10KV 35KV 66KV 110KV 220KV
Low Voltage: 400V 6.3KV 10KV 35KV
Rated Power: 30kVA 50kVA 100kVA 200kVA 315kVA
500kVA 630kVA 800kVA 1000kVA 1250kVA 1600kVA
2000kVA 2500kVA 3150kVA 4000kVA 5000kVA 63000kVA
Connection symbol: YNd11, Dyn11
Category
Power Transformers
 
Send Inquiry
Description
Technical Parameters

Products Description

Utility-grade transformers are widely used in transmission and distribution networks to convert electrical energy between different voltage levels. They assist power companies in delivering electrical energy to residential areas, commercial buildings, industrial facilities, and various infrastructure projects. According to the power grid design plan, transformers can be installed in substations, distribution nodes or industrial power supply stations. Tianjin Kechang International Trade Co., Ltd. provides utility-grade transformers for power distribution projects with various voltage levels and capacity requirements. Our product range covers various needs from power distribution applications to large-capacity power systems. Each transformer can be customized and configured according to the electrical technical specifications, installation environment and applicable technical standards of the project.

Learn Morn>>

11 0416 power transformer

 

Product Design&Structure

 

 

 

Core and winding design

The iron core is made of oriented silicon steel, which is selected for its excellent magnetic properties and potential to reduce no-load loss. The core structure is determined by the rated voltage, capacity and performance requirements. The windings can be made of copper or aluminum conductors according to agreed specifications. Its layout, insulation and mechanical support design are designed to withstand the electrical and thermal stresses generated under normal operation and specified fault conditions. The final winding configuration also determines the voltage ratio and coupling group of the transformer.

 

Fuel tank and cooling system

For oil-immersed power transformers, the fuel tank is equipped with a body (active component) and an insulating oil; the insulating oil not only provides electrical insulation, but also is responsible for transmitting and dissipating the heat generated by the windings and iron cores.Depending on the design and capacity, the transformer may adopt a corrugated fuel tank or a reinforced fuel tank structure.Protective coating can be selected according to the installation environment. Depending on the specific model, typical accessories may include oil level gauges, thermometers, pressure relief devices, oil drain valves, and hoisting points. The sealing system and fuel tank structure are designed to ensure safe operation and prevent oil spills.

 

Insulation and voltage regulation

The insulation system isolates the winding from other charged components to provide the required dielectric strength.Its design depends on the rated voltage, insulation level and applicable standards. When the voltage needs to be adjusted, a non-excitation voltage regulating tap switch or an on-load voltage regulating tap switch can be selected. The available tap range and adjustment method depend on the selected design. The connection group (such as Dyn11 and YNd11) must match the phase relationship and grounding requirements of the power grid.

 

Application of utility transformers

Utility transformers support a variety of power projects:

*Substations: Connect different voltage levels in the transmission and distribution network.

*Public power distribution:  Power supply for residential areas, commercial areas and municipal infrastructure.

*Industrial power system: Power supply for factories, mining facilities, processing plants and other large loads.

*Renewable energy projects: Support the electrical connection of solar power plants and other power generation facilities.

*Infrastructure projects:  Serve railways, data centers, water treatment plants and large-scale building development projects. The appropriate rated capacity should be determined based on the actual load, expected demand growth, operating conditions and system design.

 

 

Packaging and Shipping

 

packaging and shipping

 

Model Number Rated Volume Quantity
(KVA)
Voltage Combination(KV) Connection Group Label No-load Loss
(W)
Load Loss
(W)
No-load Electricity
(%)
Short Circuit Resistance
(%)
High
Voltage
High Voltage Tap Range Low Voltage
S13-630 630 35 ±5%

or

±2×2.5%
3.15

6.3

10.5
yd11 580 7860 0.65 6.5
S13-800 800 690 9400 0.65 6.5
S13-1000 1000 810 11500 0.65 6.5
S13-1250 1250 980 13900 0.55 6.5
S13-1600 1600 1180 16600 0.45 6.5
S13-2000 2000 1520 18300 0.45 5.5
S13-2500 2500 1790 19600 0.45 6.5
S13-3150 3150 35

38.5
±5%
or
±2×2.5%
3.15
6.3
10.5
2130 23000 0.45 7
S13-4000 4000 2530 27300 0.45 7
S13-5000 5000 3020 31300 0.45 7
S13-6300 6300 3670 35000 0.45 8
S13-8000 8000 35

38.5
±5%

or

±2×2.5%
3.15
3.3
6.3
6.6
10.5
ynd11 5040 38400 0.35 8
S13-10000 10000 6090 45300 0.35 8
S13-12500 12500 7000 53800 0.30 8
S13-16000 16000 8470 65800 0.30 8
S13-20000 20000 10080 79500 0.30 8
S13-25000 25000 11900 94000 0.25 10
S13-31500 31500 14140 112000 0.25 10

Hot Tags: utility transformers, China utility transformers manufacturers, suppliers, factory, 5kva continuous transformer, 3150 kva transformer, 112 kva transformer, Power Distribution Transformer, 220 volt ac to dc converter, 10kw transformer