Product Introduction

Step-down transformers are designed to convert high-voltage or medium-voltage energy into a lower voltage suitable for power distribution and equipment operation. It plays an important role in industrial power systems, commercial buildings, substations and various infrastructure projects.
Kechang Electric provides step-down transformers suitable for a variety of power supply environments, covering a variety of voltage combinations and rated capacities. According to the project requirements, the equipment can convert input voltages such as 10 kV, 11 kV, 20 kV or 33 kV to low-voltage outputs such as 400 V, 415 V or 433 V.
Unlike fixed standard configurations, each project may require different electrical solutions. When designing transformers, our engineering team will comprehensively consider the input voltage of the power grid, the connection load, the installation environment, and future expansion needs.
Product Features
The main characteristics of Kechang step-down transformer
Stable output under load fluctuations
Industrial loads are not always constant. The operation of motors, pumps, compressors and various production machinery may cause significant changes in power demand. Our transformer design fully takes into account the load characteristics and temperature rise factors to ensure that a reliable power supply can be maintained during normal operation fluctuations.
01
Multiple voltage regulation methods
For application scenarios where the supply voltage may fluctuate, we provide a variety of tap switch adjustment schemes. The non-excitation tap switch (Off-circuit tap changer) can adjust the voltage during the planned power outage; if the project has special needs, the on-load tap switch (OLTC) can also be selected to adjust the voltage ratio without interrupting the power supply.
02
Configurable cooling and protection system
Depending on the installation environment, customers can choose oil-immersed or dry-type structures. In terms of cooling methods, oil-immersed transformers can be configured with oil-immersed self-cooling (ONAN) or oil-immersed air-cooling (ONAF); dry transformers can be configured with air-cooled (AN) or air-cooled (AF). The fuel tank design, shell protection level and accessories can be configured according to indoor or outdoor installation requirements.
03
Adapt to a variety of electrical systems
The transformer can adopt a suitable coupling group, neutral point arrangement and terminal connection form to match the downstream power distribution system. For integrated projects, transformers can also be matched and coordinated with high-voltage switchgear, low-voltage distribution panels and compact substations.
04
Inspection and technical documents
Before delivery, each equipment must pass the corresponding factory inspection and conventional electrical tests. We can provide test reports, technical drawings, nameplate information and installation documents to support customer acceptance and project handover.
05
Product application scenarios

Industrial manufacturing: provide the required operating voltage for motors, production lines, compressors and factory auxiliary systems.
Commercial buildings: used in shopping centers, office buildings, hospitals, hotels and other places to meet the needs of various electrical loads for low-voltage power distribution.
Mining and heavy industry: provide power support for processing plants, pumping stations, ventilation systems, and other industrial facilities operating under harsh operating conditions.
Distribution substation: Converts the medium voltage to the voltage required on the user side to serve the local distribution network and end users.
Solar energy and renewable energy projects: according to the electrical design plan of the project, it can be integrated into the auxiliary power supply and distribution system.

One-stop power solutions in China
Kechang Electric provides step-down transformer solutions for distributors, EPC contractors, industrial users and power engineering projects.Please inform us of your voltage requirements, rated capacity and installation conditions, and we will provide you with corresponding technical solutions.
Technical Specification
| Model Number | Rated Volume Quantity (kVA) |
Voltage Combination(kV) | Connection Group Label | No-load Loss (W) |
Load Loss (W) |
No-load Electricity (%) |
Short Circuit Resistance (%) |
||
| High Voltage |
High Voltage Tap Range | Low Voltage | |||||||
| S13-630 | 630 | 35 | ±5% or ±2×2.5% |
3.15 6.3 10.5 |
yd11 | 580 | 7860 | 0.65 | 6.5 |
| S13-800 | 800 | 690 | 9400 | 0.65 | 6.5 | ||||
| S13-1000 | 1000 | 810 | 11500 | 0.65 | 6.5 | ||||
| S13-1250 | 1250 | 980 | 13900 | 0.55 | 6.5 | ||||
| S13-1600 | 1600 | 1180 | 16600 | 0.45 | 6.5 | ||||
| S13-2000 | 2000 | 1520 | 18300 | 0.45 | 5.5 | ||||
| S13-2500 | 2500 | 1790 | 19600 | 0.45 | 6.5 | ||||
| S13-3150 | 3150 | 35 38.5 |
±5% or ±2×2.5% |
3.15 6.3 10.5 |
2130 | 23000 | 0.45 | 7 | |
| S13-4000 | 4000 | 2530 | 27300 | 0.45 | 7 | ||||
| S13-5000 | 5000 | 3020 | 31300 | 0.45 | 7 | ||||
| S13-6300 | 6300 | 3670 | 35000 | 0.45 | 8 | ||||
| S13-8000 | 8000 | 35 38.5 |
±5% or ±2×2.5% |
3.15 3.3 6.3 6.6 10.5 |
ynd11 | 5040 | 38400 | 0.35 | 8 |
| S13-10000 | 10000 | 6090 | 45300 | 0.35 | 8 | ||||
| S13-12500 | 12500 | 7000 | 53800 | 0.30 | 8 | ||||
| S13-16000 | 16000 | 8470 | 65800 | 0.30 | 8 | ||||
| S13-20000 | 20000 | 10080 | 79500 | 0.30 | 8 | ||||
| S13-25000 | 25000 | 11900 | 94000 | 0.25 | 10 | ||||
| S13-31500 | 31500 | 14140 | 112000 | 0.25 | 10 | ||||
Hot Tags: step down transformer, China step down transformer manufacturers, suppliers, factory, 5kva continuous transformer, 3150 kva transformer, 112 kva transformer, Power Distribution Transformer, 220 volt ac to dc converter, 10kw transformer