Vacuum Disconnector

Vacuum Disconnector

Details
Rated Voltage:10KV 35KV 66KV
Rated Current:630A 1250A 2000A
Rated Short-Time Withstand Current:25kA 31.5kA 40kA
Insulation Level:LI75kV/AC35kV LI170kV/AC70kV LI325kV/AC145kV
Protection Level:IP44 IP54
Frequency:50Hz 60Hz
Mechanical Service Life:10000 Operations
Category
Circuit Breaker
 
Send Inquiry
Description
Technical Parameters

Product Introduction

Reliable Isolation of Medium Voltage Power Distribution

 

A stable power distribution system depends on reliable switching equipment and clear electrical isolation.Kechang vacuum isolation switches are designed for medium voltage power distribution applications to help operators isolate circuits during inspection, maintenance, and equipment replacement.It can be integrated into compatible switchgear and substation systems to support safe operation and efficient maintenance.

 

Vacuum isolation switches are suitable for distribution networks, industrial facilities, commercial buildings and infrastructure projects, and can be configured according to project voltage, rated current, installation space and operating requirements.Its compact structure and practical operating design make it suitable for new installation and switchgear renovation projects.

.

30000 times Indoor Solid Sealed Vacuum Circuit Breaker

Product Advantages

Stable Electrical Connection and Insulation

The contact system and insulation structure are important components of the isolation switch. During normal operation, the contacts must carry the specified current without overheating, and the insulating components must be able to withstand the electrical stress associated with the rated voltage.

Kechang vacuum isolation switch can be equipped with suitable conductive contacts, insulating brackets and operating mechanisms according to the requirements of the selected model.For designs using vacuum circuit breakers, the vacuum chamber can provide the environment required for its expected switching function.

It is essential to distinguish between isolation switches and vacuum circuit breakers. Standard isolation switches are used to establish isolation gaps and are usually not used to cut off loads or short circuit currents. These tasks must be completed by specially designed and rated equipment. Therefore, before the equipment is put into use, the complete switch configuration should be confirmed.
1250A Withdrawable Type Vacuum Circuit Breaker
 

Practical Mechanical Designz


The operating mechanism will affect the performance of the switch and daily maintenance. A well-designed mechanism helps to maintain the consistency of opening and closing actions and reduces the risk of problems caused by loose connections or component wear.

Depending on the model, manual or electric operating mechanisms can be provided. The choice depends on the installation layout, frequency of operation, and whether remote operation is required. The mechanical and electrical interlocking devices can also be configured according to the relevant circuit breakers and grounding switches.

Regular inspections are still essential. The operator should check the mechanism, contact condition, insulating surface and interlocking assembly in accordance with the manufacturer's instructions. The actual maintenance cycle depends on the product design and on-site conditions.

630A Withdrawable Type Vacuum Circuit Breaker
 

Interlocking ensures safer operation

Incorrect switching sequence can cause serious risks during electrical maintenance. Therefore, the isolation switch should be operated in coordination with other switchgear in the switchboard.

Appropriate interlocking devices help prevent incompatible operations, such as operating a ground switch while the relevant circuit is still charged. The specific interlocking device depends on the design of the switchgear and the operating procedures of the installation specification.

Before starting maintenance, the circuit must be isolated and an approved procedure must be used to verify that there is no voltage. The interlocking device is an additional safety measure and cannot replace the correct electrical safety operating procedures.

Operating environment
 

Applicable to Different on-site Conditions

Medium voltage equipment is installed in a variety of environments, from indoor electrical rooms to outdoor substations. Temperature, humidity, dust, altitude and shell protection will all affect the choice of equipment.

Kechang will consider these conditions when formulating a vacuum isolation switch solution. According to the model, you can choose the appropriate installation method, insulation components, housing and connection structure to meet the project needs. For places with high humidity or high air pollutants, the required protective measures should be confirmed during the technical review period.

The rated environmental limits should always be checked with the product data sheet. This is particularly important for outdoor installations and projects located at high altitudes.

Product Applications

Rating and project configuration

Kechang provides technical selection support for medium voltage vacuum isolation switches used in power distribution and industrial applications. The available configurations depend on the product family and should be confirmed according to the required specifications.
 

1. Rated voltage: 6 kV to 35 kV, depending on model availability

2. Rated current: 630 A to 3150 A, depending on model availability

3. Operation method: manual or electric operation (if any)

4. Installation method: choose according to the structure of the switchgear

5. Documents: applicable technical drawings and inspection documents

modular-1
One-stop Vacuum Disconnector Supplier in China

Send your inquiry about vacuum disconnectors to us and get reliable medium-voltage isolation solutions for your power projects. With our robust electrical switchgear components, you can secure circuit isolation, enhance operational safety, and unlock new opportunities for your power distribution and substation projects.

Product Specifications

 

Number Parameter name Unit Technical Parameters
1 Rated voltage kV 12
2 Rated short-time frequency withstand voltage (1 min) kV 42
3 Rated lightning impulse withstand voltage (peak) kV 75
4 Rated frequency Hz 50
5 Rated current A 630/1250/1600/2000/2500/3150/4000
6 Rated short-circuit breaking current kA 20 25 31.5 40
7 Rated short-time withstand current kA 20 25 31.5 40
8 Rated short circuit duration S 4
9 Rated short-circuit closing current kA 50 63 80 100
10 Rated peak withstand current kA 50 63 80 100
11 Number of rated short-circuit current starts times 30 30 30 20
12 Rated individual capacitor bank opening current A ≤630
13 Rated back-to-back capacitor bank opening current A ≤400
14 Rated capacitor bank closing inrush current kA 12.5(frequency≤1000Hz)
15 Closing time ms ≤80
16 Split time ms Maximum Voltage ≤40
ms Rated Voltage ≤50
ms Minimum Voltage ≤60
17 Time of ignition ms ≤15
18 Mechanical life (M2) times 30000
19 Allowable cumulative thickness of dynamic and static contact wear mm 3
20 Rated closing operating voltage V AC/DC 220, AC/DC 110
21 Rated breaking operating voltage V AC/DC 220, AC/DC 110
22 Rated operating voltage of energy storage motor V AC/DC 220, AC/DC 110
23 Rated power of energy storage motor W 80 (40KA Motor speed 100W)
24 Energy storage time s ≤15
25 Contact opening distance mm 9±1
26 Over traveling distance mm 3.5±0.5
27 Contact closing bounce time ms ≤2
28 Three-phase switching and closing non-synchronous ms ≤2
29 Contact splitting rebound amplitude mm ≤3
30 Contact closing contact pressure kA 20 25 31.5 40
N±8% 2200 2500 3100 4750
31 Average breaking speed (contacts separated by 6mm) m/s 1.1±0.2
32 Average closing speed (6mm contact closure) m/s 0.6±0.2
33 Dominant electric circuit resistance A 630 1250 1600-2000 ≥2500
34 μΩ ≤50 ≤45 ≤35 ≤25
Rated operating sequence (1) 20~31.5KA   Minutes - 0.3s - combined minutes - 180s - combined minutes
35 Rated sequence of operation (2) 40KA   Minutes - 0.3s - combined minutes - 180s - combined minutes
Secondary circuit frequency withstand voltage (1min) V 2000

Hot Tags: vacuum disconnector, China vacuum disconnector manufacturers, suppliers, factory, outdoor circuit breaker, hv circuit breaker, dc circuit breaker, blown circuit breaker, standard circuit breaker, industrial circuit breaker

Send Inquiry
Get Support for Your Power‑Distribution Projects

With our patented technologies, feel free to send your project-related inquiries via phone,
email or our online form. Our electrical-engineering specialists will reply to you promptly.

Submit Your Inquiry