SF6-Free Solid Insulation

Solid insulated ring main unit (RMU) is a medium voltage switchgear solution specially developed for reliable power distribution needs in the industrial, commercial and infrastructure fields.Unlike traditional inflatable (gas insulated) equipment, it uses epoxy resin as the main insulating medium. While achieving a compact structure, there is no need to use sulfur hexafluoride (SF6) gas at all. Kechang's solid insulated ring main unit integrates vacuum circuit breakers, isolation switches, grounding switches and bus connections in an insulated housing. The key conductive components are encapsulated using the APG (automatic pressure gel) process to form a solid insulating layer around the core electrical components. This design not only ensures the long-term stability of insulation properties, but also eliminates gas-related inspections and maintenance work.
Product Feature
The main characteristics of solid insulated ring network cabinet

1. SF6-free solid insulation technology
The switchgear is insulated with epoxy resin, replacing SF6 gas. The APG pouring process provides mechanical support and electrical insulation for the internal conductive components. Combined with vacuum arc extinguishing technology, it can not only achieve reliable switching operation, but also completely eliminate the environmental hazards caused by SF6 gas leakage.
The solid insulation structure also achieves a more compact layout, which is very suitable for substations and distribution rooms with limited installation space.
2. Sealed structure suitable for harsh environments
The primary circuit components are encapsulated in a solid insulation system, which effectively protects against moisture, dust and external pollution. Depending on the configuration of the equipment, some sealing components can reach the IP67 protection level.
The metal shell has been anticorrosive treatment to enhance its durability in industrial environments or outdoor installation conditions. The equipment can be configured for a variety of operating environments, including high humidity, dusty places and coastal areas.


3. Compact modular configuration
The modular design allows the flexible combination of different functional units according to the specific needs of the distribution network. Common configurations include load switches, vacuum circuit breakers, isolation switches, and grounding switches.
When the power distribution system needs to be expanded, corresponding functional modules can be added according to the busbar layout and engineering design requirements. This design provides project contractors with greater flexibility during the system planning and installation phase.
4. Integrated safety interlock
Electrical safety is the core element of medium voltage power distribution equipment. The ring main unit (RMU) is equipped with a mechanical interlocking between the switching operation and the grounding operation, which is designed to prevent the wrong sequence of operations.
Through the visual position indicator, the operator can confirm the working status of the switching mechanism. All conductive housings and accessible metal parts are connected to the grounding system to ensure the safety of personnel during equipment operation and maintenance.

Application area
Kechang solid insulated ring main unit is suitable for the following medium voltage power distribution systems:
- Industrial plants and manufacturing facilities,
- Commercial buildings and shopping centers,
- Solar power plants and renewable energy projects,
- Urban distribution network -Hospitals, data centers and infrastructure,
- Mines and other industrial sites with harsh environments Customized solid insulated ring main unit solution.
Product Specifications
| project | parameter | |||||||||
| Load switchgear(C) | Combined elecctric cabinet(F) | Circuit breaker cabinet(V) | ||||||||
| Rated voltage | 12V | |||||||||
| Rated frequency | 50HZ | |||||||||
| Rated current | 630A | 1250A(Depends on fuse current) | 630A/1250A | |||||||
| Rated transfer current | / | 1750A | / | |||||||
| Cable charging break current | 40A | 25A | ||||||||
| No-load transformer breaking current | 16A | 16A | ||||||||
| Rated switching times of active load | 100次 | / | / | |||||||
| Rated number of short circuit breakering | / | / | ≥30次 | |||||||
| Rated short-time tolerable current |
The primary loop | 20KA/4S | / | 20KA/4S,31.5KA/4S | ||||||
| Grounding switch | 20KA/4S | / | 20KA/4S,31.5KA/4S | |||||||
| Rated short circuit closing current |
The primary loop | 50KA | Limited by high voltage fuse | 50KA/80KA | ||||||
| Grounding switch | 50KA | 50KA/80KA | ||||||||
| 1 mimute power frequency voltage withstand |
Interphase with and against the ground | 42kv | ||||||||
| Fracture | 48KV | |||||||||
| lighting shock withstand voltage | Interphase with and against the ground | 75KV | ||||||||
| Fracture | 85KV | |||||||||
| Mechanical life | The main switch | ≥5000次 | ≥10000次 | |||||||
| Grounding switch | ≥3000次 | |||||||||
| Main circuit resistance | ≤120μΩ | ≤400μΩ | ≤200μΩ | |||||||
| SF6 gas pressure rating (20℃) | 0.035MPa | |||||||||
| Annual leakage rate of SF6 gas | 0.01% | |||||||||
| Rated power supply voltage of secondary loop | AC220V/DC110DC48V/DC24V | |||||||||
| 2KV | ||||||||||
| Protection grade | Aeration tank | IP67 | ||||||||
| Shell and operating mechanism | IP4X | |||||||||
Hot Tags: solid insulated ring main unit, China solid insulated ring main unit manufacturers, suppliers, factory, hv rmu, Environmentally Friendly Gas Insulated Ring Main Unit, 3 phase ring main, Outdoor Ring Main Unit, 13 8 kv ring main unit, 33kv ring main unit